应用与工作电压大于100 伏交流电“NoBurn”FTS29OM16-100/100 V 电缆标有 CEI 20-105 (PH 120)
表明它们符合 CEI EN 50200 的防火要求标准,规定在 820°C 下的最短运行时间为 120 分钟被测电缆,受到直接火灾和机械冲击
They can be used connecting the devices of automatic fixed systems ofdetection and manual fire alarm systems, connected or not to extinguishingsystems or to another protection system (both active and passive type),intended to be installed in buildings, no matter the intended use. They arenot suitable for other uses such as emergency lighting, power supply offorced smoke and heat evacuation systems, electric lock or emergencycontrols or other similar applications with operating voltage greater than100 V ACNoBurn” FTS29OM16-100/100 V cables are marked CEI 20-105 (PH 120)to indicate that they are fire-resistant in accordance with CEI EN 50200standards, providing for a minimum operating time of 120 minutes at 820°Cof the tested cable, subject to direct fire and mechanical shock.
标准/STANDARDS
- CPR EN 50399
- CEI EN/IEC 60332-1-2
- CEI 20-45
- CEI EN 50200 (O ≤ 20 mm)
- CEI EN 61034-2
- CEI EN 50362 (O > 20 mm)
- CEI EN/IEC 60228
- CEI 20-11
- CEI EN 50267-2-1
- CEI EN 60754-2
- EN 50575:2014+A1:2016
电缆结构/ CONSTRUCTION FEATURES
导体
Conductor
软退火铜线,5 级。覆盖防火云母带
Soft annealed copper cord, class 5. Covered with fire proof mica tape
绝缘
Insulation
热塑性聚烯烃 S29,具有低毒性和腐蚀性烟雾和气体
Thermoplastic polyolefin S29, with low development of toxic and corrosivefumes and gases
芯线颜色
Cores Colour
1-5芯分色,>5芯编码区分
1 to 5 core color separation, > 5 core code
绕包/Screen
带镀锡铜排扰线的铝/聚酯胶带
Aluminium/polyester tape with tinned copper drain wire